Business, Finance, Economics, Accounting, Operations Management, Computer Science, Electrical Engineering, Mechanical Engineering, Civil Engineering, Chemical Engineering, Algebra, Precalculus, Statistics and Probabilty, Advanced Math, Physics, Chemistry, Biology, Nursing, Psychology, Certifications, Tests, Prep, and more.
Post Reply
answerhappygod
Site Admin
Posts: 899604
Joined: Mon Aug 02, 2021 8:13 am

600 VOLT, 3 PHASE, WYE CONNECTED SYNCHRONOUS MOTOR CONSUMES 400 KW AT 0.9 POWER FACTOR LEADING. RESISTANCE PER COIL = 0.

Post by answerhappygod »

600 VOLT, 3 PHASE, WYE CONNECTED SYNCHRONOUS MOTOR CONSUMES 400KW AT 0.9 POWER FACTOR LEADING. RESISTANCE PER COIL = 0.06 OHM,SYNCHRONOUS REACTANCE PER COIL = 0.12 OHM. STRAY POWER LOSS = ½CORE LOSS, CORE LOSS = 1/8 COPPER LOSS. WHAT IS THE COUNTER EMF ANDEFFICIENCY OF THE MACHINE?
a. 607.49 V b. 605.36 V c. 606.94 V d. 616.49 V