Business, Finance, Economics, Accounting, Operations Management, Computer Science, Electrical Engineering, Mechanical Engineering, Civil Engineering, Chemical Engineering, Algebra, Precalculus, Statistics and Probabilty, Advanced Math, Physics, Chemistry, Biology, Nursing, Psychology, Certifications, Tests, Prep, and more.
Post Reply
answerhappygod
Site Admin
Posts: 899603
Joined: Mon Aug 02, 2021 8:13 am

Consider a Carnot refrigeration cycle executed in a closed system in the saturated liquid-vapor mixture region using 1.1

Post by answerhappygod »

Consider A Carnot Refrigeration Cycle Executed In A Closed System In The Saturated Liquid Vapor Mixture Region Using 1 1 1
Consider A Carnot Refrigeration Cycle Executed In A Closed System In The Saturated Liquid Vapor Mixture Region Using 1 1 1 (14.25 KiB) Viewed 109 times
Consider a Carnot refrigeration cycle executed in a closed system in the saturated liquid-vapor mixture region using 1.16 kg of refrigerant-134a as the working fluid. It is known that the maximum absolute temperature in the cycle is 1.2 times the minimum absolute temperature, and the net work input to the cycle is 22 kJ. If the refrigerant changes from saturated vapor to saturated liquid during the heat rejection process, determine the minimum pressure in the cycle. The minimum pressure in the cycle is 795 kPa.