The output power of a transformer at 50% rated load is 0.95 pu. At full rated load, copper coil losses are 0.01 pu, and

Business, Finance, Economics, Accounting, Operations Management, Computer Science, Electrical Engineering, Mechanical Engineering, Civil Engineering, Chemical Engineering, Algebra, Precalculus, Statistics and Probabilty, Advanced Math, Physics, Chemistry, Biology, Nursing, Psychology, Certifications, Tests, Prep, and more.
Post Reply
answerhappygod
Site Admin
Posts: 899603
Joined: Mon Aug 02, 2021 8:13 am

The output power of a transformer at 50% rated load is 0.95 pu. At full rated load, copper coil losses are 0.01 pu, and

Post by answerhappygod »

The output power of a transformer at 50% rated load is 0.95 pu.At full rated load, copper coil losses are 0.01 pu, and core losses0.018 pu. Calculate the transformer efficiency at 50% of ratedload. [Answer: 97.9%. Efficiency = Pout/Pin, Pin = Pout + Plosses.Core losses stay the same independent of load, but the power lostfrom the copper coil is proportional to the square of the powerused by the load, and therefore the square of the efficiency.]