Business, Finance, Economics, Accounting, Operations Management, Computer Science, Electrical Engineering, Mechanical Engineering, Civil Engineering, Chemical Engineering, Algebra, Precalculus, Statistics and Probabilty, Advanced Math, Physics, Chemistry, Biology, Nursing, Psychology, Certifications, Tests, Prep, and more.
Post Reply
answerhappygod
Site Admin
Posts: 899603
Joined: Mon Aug 02, 2021 8:13 am

3. What is the maximum phase-to-neutral PEAK voltage of a 34.5 kV nominal distribution system? Assume that, during norma

Post by answerhappygod »

3 What Is The Maximum Phase To Neutral Peak Voltage Of A 34 5 Kv Nominal Distribution System Assume That During Norma 1
3 What Is The Maximum Phase To Neutral Peak Voltage Of A 34 5 Kv Nominal Distribution System Assume That During Norma 1 (39.37 KiB) Viewed 69 times
3. What is the maximum phase-to-neutral PEAK voltage of a 34.5 kV nominal distribution system? Assume that, during normal operation the power system voltage may reach a maximum of 1.05 pu. I a) 20.9 kV b) 29.6 kV c) 36.2 KV