11. R-134a enters a steady state, isentropic compressor as a saturated vapor at 140 kPa, with the volumetric flowrate at
11. R-134a enters a steady state, isentropic compressor as a saturated vapor at 140 kPa, with the volumetric flowrate at the compressor inlet being 8.5 m3/hr. The refrigerant exits the compressor at a pressure of 1200 kPa. a) Determine the input power to the isentropic compressor, in units of kW. b) Determine the actual input power, in kW, of this compressor if it has an isentropic efficiency of 75%.