Business, Finance, Economics, Accounting, Operations Management, Computer Science, Electrical Engineering, Mechanical Engineering, Civil Engineering, Chemical Engineering, Algebra, Precalculus, Statistics and Probabilty, Advanced Math, Physics, Chemistry, Biology, Nursing, Psychology, Certifications, Tests, Prep, and more.
Post Reply
answerhappygod
Site Admin
Posts: 899604
Joined: Mon Aug 02, 2021 8:13 am

1. A 2500kVA, 6600V synchronous turbo alternator is operating at full load and 0.8 pf lagging. This machine has a synchr

Post by answerhappygod »

1. A 2500kVA, 6600V synchronous turbo alternator is operating at
full load and 0.8 pf lagging. This machine has a synchronous
reactance per phase is 10.4Ω and a negligible resistance. Compute
for the terminal voltage. Use two decimal
places.
2. A 3-phase, Y-connected, 6-pole, 60Hz generator has X S
=1Ω , negligible o rS (stator resistance), and Lsf = 0.2H . The
machine operates at a power angle of 31.48 with a field current of
100A. The line-to-neutral terminal voltage is 2400Vrms. Find the
line current. Magnitude only. Use 1 decimal
place